Amp hours to buy for your daily use, in lithium and lead acid, and the peak draw floor most charts leave out. Every cell is worked from a stated basis you can check.

Published30 October 2026
Sources5 cited

A battery bank chart has to answer two questions, and most of them only answer one. The first is energy: how many amp hours get you through the days between charges. The second is current: whether the bank can feed your heaviest load without being worked harder than it should be. The bank you buy is the larger of the two answers.

So this page has a chart for each, kept apart. Every cell is worked from the same sums the battery bank calculator uses, with the basis written out under each table, so you can check me.

Count watt hours first

Amp hours only mean something at a stated voltage. Watt hours are amp hours times volts, so an amp hour at 24 volts holds twice the energy of an amp hour at 12 volts. Start every bank in watt hours and convert at the end.

There are two ways to get a daily figure.

Add it up. For each load, watts times hours a day. The watts are on the rating plate. For anything that runs through the inverter, divide by the inverter’s efficiency from its datasheet, because the battery pays for the inverter’s losses as well as the load.

Measure it. A battery monitor with a shunt counts what actually leaves the battery, inverter losses and forgotten standby loads included. If the rig is already running, a few ordinary days on a monitor beats any list I could write for you.

Either way, you want watt hours per day, at the battery.

Chart 1: lithium (LiFePO4) at 12 volts

Find your daily use down the side and the number of days between charges across the top. Each cell is the smallest nameplate capacity, in whole amp hours, that covers it.

Daily use Amp hours a day at 12 V 1 day 2 days 3 days
250 Wh 20.8 Ah 27 Ah 53 Ah 79 Ah
500 Wh 41.7 Ah 53 Ah 105 Ah 157 Ah
750 Wh 62.5 Ah 79 Ah 157 Ah 235 Ah
1,000 Wh 83.3 Ah 105 Ah 209 Ah 313 Ah
1,500 Wh 125 Ah 157 Ah 313 Ah 469 Ah
2,000 Wh 166.7 Ah 209 Ah 417 Ah 625 Ah
2,500 Wh 208.3 Ah 261 Ah 521 Ah 782 Ah
3,000 Wh 250 Ah 313 Ah 625 Ah 938 Ah
4,000 Wh 333.3 Ah 417 Ah 834 Ah 1,250 Ah

The basis, so you can check me:

  • 12 volts. Amp hours are watt hours divided by 12.
  • 80 percent usable. This is the calculator’s planning figure for LiFePO4. Why 80 and not 100 is further down.
  • 77 °F (25 °C). No cold derate. Cold is covered below.
  • No charging during the days counted. No solar, no alternator, no shore power. That is the case you are sizing for when the weather closes in.

The sum: daily watt hours, times days, divided by 12, divided by 0.8. Read one cell. 1,000 Wh a day for two days is 2,000 Wh, which is 166.7 Ah at 12 volts. Divide by 0.8 and you need 208.3 Ah of nameplate, so the chart says 209 Ah.

Chart 2: lead acid (AGM, gel and flooded) at 12 volts

Same layout, same basis, with one change.

Daily use Amp hours a day at 12 V 1 day 2 days 3 days
250 Wh 20.8 Ah 42 Ah 84 Ah 125 Ah
500 Wh 41.7 Ah 84 Ah 167 Ah 250 Ah
750 Wh 62.5 Ah 125 Ah 250 Ah 375 Ah
1,000 Wh 83.3 Ah 167 Ah 334 Ah 500 Ah
1,500 Wh 125 Ah 250 Ah 500 Ah 750 Ah
2,000 Wh 166.7 Ah 334 Ah 667 Ah 1,000 Ah
2,500 Wh 208.3 Ah 417 Ah 834 Ah 1,250 Ah
3,000 Wh 250 Ah 500 Ah 1,000 Ah 1,500 Ah
4,000 Wh 333.3 Ah 667 Ah 1,334 Ah 2,000 Ah
  • 50 percent usable instead of 80. Everything else is as above.

The sum is the same with 0.5 in place of 0.8, so lead acid needs 1.6 times the nameplate of lithium for the same energy. Take the same row as before. 1,000 Wh a day for two days needs 334 Ah of lead acid against 209 Ah of lithium.

AGM, gel and flooded share one chart because the calculator plans all three at the same usable depth. If the datasheet for your battery gives a different figure, divide by that instead.

One thing this chart does not have to worry about. Lead acid capacity is quoted over a slow discharge, and Victron’s gel and AGM datasheet rates it over 20 hours. Spread over a whole day, every row here draws less current than that, so the penalty for working lead acid hard does not touch these figures. It comes back in the peak chart.

Why lithium gets 80 percent and lead acid 50

Battle Born’s comparison of the three chemistries puts the usable depth of lead acid and AGM at about 50 percent if you want the battery to last. Go deeper as a habit and you pay for it in battery life.

The same comparison rates lithium for much deeper use. I still plan lithium at 80 percent. It is headroom, and the cold eats into it before anything else does. It is also the figure the calculator uses. If you would rather plan yours at 100 percent, multiply the lithium column by 0.8.

Chart 3: the peak draw floor

The energy charts treat your use as if it were spread evenly across the day. It is not. A microwave, a kettle or a hair dryer on the inverter pulls a lot of current for a few minutes, and a bank sized on energy alone can be too small to feed it.

The limit is a C-rate, which is amps per amp hour of nameplate. At 0.5C, a 200 Ah bank gives 100 A. Find your heaviest load, in watts drawn from the battery, and read across. Each cell is the smallest nameplate capacity that keeps that load at or under the rate.

Peak load from the battery Amps at 12 V LiFePO4 at 0.5C Lead acid at 0.2C
300 W 25 A 50 Ah 125 Ah
500 W 41.7 A 84 Ah 209 Ah
750 W 62.5 A 125 Ah 313 Ah
1,000 W 83.3 A 167 Ah 417 Ah
1,500 W 125 A 250 Ah 625 Ah
2,000 W 166.7 A 334 Ah 834 Ah
2,500 W 208.3 A 417 Ah 1,042 Ah
3,000 W 250 A 500 Ah 1,250 Ah

The basis:

  • Lithium at 0.5C. This is the calculator’s planning rate, and it is cautious on purpose. Your battery’s datasheet gives its own continuous discharge rating, and that is the number that counts. If it allows 1C, halve the lithium column.
  • Lead acid at 0.2C. That is the current that would empty the label in five hours, and it is the calculator’s planning rate. Lead acid gives less than its label when it is worked hard. Victron’s SmartShunt manual explains this with the Peukert exponent: an ideal battery has an exponent of 1.00 and the same capacity at any current, and lead acid is not ideal. Victron’s gel and AGM datasheet has a table of effective capacity against discharge time that shows the same thing. The faster the discharge, the less comes out.
  • 12 volts. Amps are watts divided by 12.
  • Watts at the battery. For a load on the inverter, take the watts on its rating plate and divide by the inverter’s efficiency from its datasheet. Say the datasheet gives 90 percent. A 1,000 W load at the plug then pulls about 1,111 W from the battery.

There is a shortcut that works at any voltage. In watt hours, the floor is the peak watts times two for lithium at 0.5C, and times five for lead acid at 0.2C.

24 volts moves the amps, not the floor

Going to 24 volts halves the current for the same load. That matters for cable, fuses and the inverter. It does not shrink this floor.

2,000 W at 24 volts is 83.3 A, and at 0.5C that needs 167 Ah of 24 volt lithium. That is the same 4,000 Wh as 334 Ah at 12 volts. The amp hour number halves because each amp hour holds twice the energy.

So if the peak is what sets your bank, 24 volts will not make the battery smaller. Moving the heavy load off the inverter will. A kettle on the stove, or the microwave saved for shore power, changes the floor. A different system voltage does not.

The amps column is still worth a second look. It is the current your main battery cable and fuse have to carry. The 12V wire size chart covers that, and on a short heavy run it is heat, not voltage drop, that sets the size.

Put the two together

Here is a worked example, with made-up numbers so the sum is easy to follow. A van uses 1,200 Wh a day at the battery, measured on a monitor. It needs two days between charges. The heaviest load is 1,000 W at the plug, through an inverter whose datasheet gives 90 percent.

Check LiFePO4 Lead acid
Energy: 2,400 Wh at 12 V 250 Ah 400 Ah
Peak: 1,111 W from the battery, 92.6 A 186 Ah 463 Ah
Buy at least 250 Ah 463 Ah

For lithium, the energy sets the bank and the peak floor sits well under it. For lead acid, the peak sets it. A 400 Ah lead acid bank would carry the energy and still be worked past its planning rate every time that load ran. The choices are a bigger bank, a lighter peak, or lithium.

What the charts leave out

Solar. The charts assume nothing goes back in. With solar, the calculator takes the array’s daily yield off your load before multiplying by the days. It never sizes below one night’s use, which it takes as half the daily load, because the panels do nothing after dark. The methodology page has the formula and the derate it uses. Enter sun hours for the worst month you will be off shore power, not the summer average.

Cold. RELiON publishes cold-weather capacity figures for lithium and for lead acid, and both fall as the temperature drops. They are one maker’s figures for its own batteries, so they are not in the chart. The calculator derates for the coldest temperature you give it.

The bigger cold problem is charging. RELiON warns that charging lithium below freezing, 32 °F (0 °C), can plate lithium inside the cell, which cuts capacity and raises resistance, and that the damage can be permanent. It sells low temperature models with a built-in heater for that reason. If the battery lives somewhere that freezes, that is a buying decision, not a sizing one.

Your battery. Usable depth and continuous discharge rating vary from one product to the next. The charts use planning figures. The datasheet for the battery in your hand beats both of them.

Recharging. The charts size a bank to run down to its planning depth. They do not tell you whether your charging can fill it again before the next run of days. That is a separate sum, and it is worth doing before you buy a bank your alternator and panels cannot keep up with.

What to do before you buy a bank

  1. Measure. A monitor on the battery for a few ordinary days, or a load list if the build is not running yet.
  2. Name the peak. The heaviest thing that runs at once, its watts, and whether it goes through the inverter.
  3. Read both charts and take the larger. For a different voltage, solar or a cold climate, put it through the battery bank calculator, which does the same sums and tells you when the peak set the answer.
  4. Check the datasheet. Its continuous discharge rating against your peak amps, and its usable depth against your planning figure.
  5. Size the cable and fuse for the peak amps, using the 12V wire size chart. Then crimp the lugs and pull-test every one before it goes anywhere near the battery.

If the bank is part of a bigger job, RV renovation costs covers where it sits in the budget.

Sources

Where this guide states a fact rather than an opinion, it came from one of these. Product names are examples of a category, not endorsements, and nothing here is sponsored.

  1. Lead-Acid vs. AGM vs. Lithium Batteries: What's the Difference? - Battle Born Batteries
  2. Battery capacity and Peukert exponent, SmartShunt manual - Victron Energy
  3. Gel and AGM batteries, datasheet - Victron Energy
  4. How do LiFePO4 batteries perform in cold temperatures? - RELiON
  5. Lithium battery cold temperature performance - RELiON

Illustrations

The diagrams on this page are illustrations, drawn to explain a concept. They are not photographs of a real cabinet and they carry no measurements, because a diagram that looks precise and is not would be worse than no diagram at all. Anything on this site with numbers on it is generated from the underlying data.