12V wire size chart (AWG to mm²)

Wire size for 12 volt runs by amps and one-way distance, the true mm² inside each AWG size, and the metric cables that look like a match but carry less copper.

Published23 October 2026
Sources6 cited

A 12 volt wire size chart is really two lookups. The first is how much copper a run needs, and that comes from the current and the distance. The second is what that copper is called in the shop you are standing in. Get the second one wrong and a correct answer to the first still leaves you with cable that is too small.

So this page does both, and keeps them apart. Every size below is worked from the same formula the DC wire size calculator uses, with the basis written out, so you can check any cell yourself.

The chart: 12 volts, 3 percent drop, copper

Find your current down the side and your distance across the top. The distance is one way, from the battery or bus bar to the load. The current has to come back again, so the sum doubles it for you. Each cell is an AWG size.

Load 5 ft (1.5 m) 10 ft (3.0 m) 15 ft (4.6 m) 20 ft (6.1 m) 25 ft (7.6 m) 30 ft (9.1 m)
5 A 18 14 12 12 10 10
10 A 14 12 10 8 8 6
15 A 12 10 8 6 6 6
20 A 12 8 6 6 4 4
25 A 10 8 6 4 4 2
30 A 10 6 6 4 2 2
40 A 8 6 4 2 2 1
50 A 8 4 2 2 1 1/0
60 A 6 4 2 1 1/0 1/0
80 A 6 2 1 1/0 2/0 3/0
100 A 4 2 1/0 2/0 3/0 4/0
150 A 2 1/0 2/0 4/0 over 4/0 over 4/0
200 A 2 2/0 4/0 over 4/0 over 4/0 over 4/0

The basis, so you can check me:

  • One-way distance, doubled in the sum for the return path.
  • Annealed copper at 68 °F (20 °C), at 1.72 × 10⁻⁸ ohm metres, the figure in Wikipedia’s resistivity table. That is 0.0172 ohm mm² per metre.
  • A 3 percent drop, which at 12 volts is 0.36 volts.
  • The smallest AWG size whose true copper area clears the requirement. True area from the table further down, not the gauge number.

The sum itself: copper area needed equals two, times the amps, times the one-way length in metres, times the resistivity, divided by the volts you can afford to lose. The full working is on the methodology page.

Read one cell and the logic is plain. 20 A over 10 ft needs 5.8 mm² of copper. 10 AWG is 5.26 mm², so it falls short, and the chart says 8 AWG. Double the distance and you double the copper.

“Over 4/0” is the chart telling you something. The run is too long or the current too high for 12 volts to make sense. Shorten the run, move the battery, or go to 24 volts. The same power at 24 volts is half the current, and you have twice as many volts to lose, so by the same sum it needs a quarter of the copper.

Why 3 percent

Blue Sea Systems splits circuits in two on its wire sizing chart. Critical circuits get a 3 percent budget: panel main feeders, bilge blowers, electronics and navigation lights. Non-critical circuits get 10 percent: general lighting, windlasses, bait pumps and general appliances.

In a van or an RV I treat anything that charges a battery, runs a fridge or feeds an inverter as critical. The cable is the cheap part of all three, and I would rather buy one size up than spend a weekend wondering whether the cable is why something misbehaves.

A 10 percent budget needs less than a third of the copper of a 3 percent one, because the area scales directly with the volts you are prepared to lose. That is why 10 percent charts look so generous. Use them for the loads they are meant for.

One trap if you cross-check against Blue Sea’s own chart. Their conductor length is the run from the source to the device and back again. Mine is one way. Read a one-way distance into a round-trip chart and you buy roughly half the copper you need.

Heat is the second check, not the first

Every cable also has a heat limit, the current it can carry before the insulation suffers. At 12 volts the drop usually sets the size long before the heat does, because the drop grows with distance and the heat limit does not.

I checked every cell above against the ampacity table the calculator uses, which is a conservative set of figures for copper bundled in a loom at 12 volts and 68 °F (20 °C). Those figures are on the reference page with their source. On the long runs, nothing is heat-limited. On the short, heavy runs it is a different story:

  • 50 A over 5 ft. 8 AWG clears the drop and sits exactly on its bundled rating of 50 A. I would go to 6 AWG.
  • 80 A over 5 ft. 6 AWG clears the drop. Its bundled rating is 65 A. Use 4 AWG.
  • 100 A over 5 ft. 4 AWG clears the drop. Its bundled rating is 85 A. Use 2 AWG.
  • 150 A and 200 A over 5 ft. 2 AWG clears the drop. Its bundled rating is 110 A. Neither load is safe on it.
  • 150 A over 10 ft. 1/0 clears the drop. Its bundled rating is 135 A.

Those are inverter feeds, alternator charging and battery-to-bus links, which is exactly where a short fat run tempts people to trust the drop chart alone. For those, size for heat first and drop second.

Three things change the heat side.

Where the cable runs. The calculator’s figures assume the cable is bundled. Manufacturers publish higher ratings for a single cable in free air, and lower ones again for hot spaces such as an engine bay. The figure you want is the one from the maker of the cable in your hand, for the way you are running it, and the insulation rating that figure assumes is printed on the jacket. Read it before you trust any amp figure, including mine.

Sizes with no published bundled figure. The calculator’s table has no 12 volt bundled rating for 1 AWG, 2/0, 3/0 or 4/0, and leaves them blank rather than guessing. For those sizes, check the manufacturer’s own table.

Warm copper in general. Copper’s resistance rises about 0.39 percent per degree Celsius, from the temperature coefficient for annealed copper in Wikipedia’s resistivity table. The chart is worked at 68 °F (20 °C). At 122 °F (50 °C) the same cable has roughly 12 percent more resistance, and a few cells sit close enough to the line to tip over. 15 A over 30 ft needs 13.1 mm², and 6 AWG is 13.3 mm². That is a cell I would size up in a hot roof cavity. The calculator corrects for temperature if you give it one. A chart cannot.

AWG to mm², the real areas

AWG is the US gauge series. Wikipedia gives its other name as the Brown & Sharpe wire gauge, which is why Australian shops still sell battery cable as B&S. Most of the rest of the world sells cable by its cross-section in square millimetres, in a fixed run of sizes set out in IEC 60228. None of those sizes lines up with an AWG size anywhere in this table.

The gauge number is not the area. 10 AWG is 5.26 mm², a little over half of 10 mm². Every three gauge numbers roughly doubles or halves the copper: 10 AWG to 4 AWG is six steps, and 5.26 mm² becomes 21.2 mm², four times as much. For stranded cable the AWG size describes the total copper area of the strands, per Wikipedia, so a stranded cable looks slightly fatter than its number suggests but carries the same copper.

AWG True copper area Metric with at least as much copper Near miss to avoid
18 0.823 mm² 1 mm² 0.75 mm²
16 1.31 mm² 1.5 mm² none
14 2.08 mm² 2.5 mm² none
12 3.31 mm² 4 mm² none
10 5.26 mm² 6 mm² none
8 8.37 mm² 10 mm² none
6 13.3 mm² 16 mm² none
4 21.2 mm² 25 mm² none
2 33.6 mm² 35 mm² none
1 42.4 mm² 50 mm² 35 mm²
1/0 53.5 mm² 70 mm² 50 mm²
2/0 67.4 mm² 70 mm² none
3/0 85.0 mm² 95 mm² none
4/0 107 mm² 120 mm² 95 mm²

The areas are Wikipedia’s AWG table. The metric sizes are the IEC 60228 series.

The last column is the one that hurts. For those four sizes the closest metric cable holds less copper than the AWG size it sits next to. Reach for it as a swap and you are undersized before the first crimp.

The same chart for metric cable

If you buy cable in Australia, the UK or Europe, or you are following a plan written there, this is the chart you want. Same lengths, same 3 percent, same copper at the same temperature. Each cell is the smallest size from the IEC 60228 series that clears the requirement, worked fresh from the area. It is not the AWG chart translated.

Load 5 ft (1.5 m) 10 ft (3.0 m) 15 ft (4.6 m) 20 ft (6.1 m) 25 ft (7.6 m) 30 ft (9.1 m)
5 A 0.75 mm² 1.5 mm² 2.5 mm² 4 mm² 4 mm² 6 mm²
10 A 1.5 mm² 4 mm² 6 mm² 6 mm² 10 mm² 10 mm²
15 A 2.5 mm² 6 mm² 10 mm² 10 mm² 16 mm² 16 mm²
20 A 4 mm² 6 mm² 10 mm² 16 mm² 16 mm² 25 mm²
25 A 4 mm² 10 mm² 16 mm² 16 mm² 25 mm² 25 mm²
30 A 6 mm² 10 mm² 16 mm² 25 mm² 25 mm² 35 mm²
40 A 6 mm² 16 mm² 25 mm² 25 mm² 35 mm² 35 mm²
50 A 10 mm² 16 mm² 25 mm² 35 mm² 50 mm² 50 mm²
60 A 10 mm² 25 mm² 35 mm² 35 mm² 50 mm² 70 mm²
80 A 16 mm² 25 mm² 35 mm² 50 mm² 70 mm² 70 mm²
100 A 16 mm² 35 mm² 50 mm² 70 mm² 95 mm² 95 mm²
150 A 25 mm² 50 mm² 70 mm² 95 mm² 120 mm² over 120 mm²
200 A 35 mm² 70 mm² 95 mm² 120 mm² over 120 mm² over 120 mm²

Two cells here are right on the line. 40 A over 30 ft needs 34.95 mm², and 80 A over 30 ft needs 69.9 mm². On paper 35 and 70 clear them. In a warm space they do not, so go up a size. The same heat check applies to the short, heavy runs as it did on the AWG chart: metric cable has no magic in it, so check the maker’s rating for anything over about 50 A on a short run.

Now compare one cell across the two charts. 20 A over 10 ft needs 5.8 mm². The AWG chart says 8 AWG, because 10 AWG at 5.26 mm² falls short. The metric chart says 6 mm², which clears it. Neither answer is a conversion of the other. They are two different cables that both do the job.

A metric plan in a US store

If a manual or a build plan gives cable in mm² and your store sells AWG, this is the smallest AWG size with at least as much copper.

Plan calls for Buy True area of what you buy
0.75 mm² 18 AWG 0.823 mm²
1 mm² 16 AWG 1.31 mm²
1.5 mm² 14 AWG 2.08 mm²
2.5 mm² 12 AWG 3.31 mm²
4 mm² 10 AWG 5.26 mm²
6 mm² 8 AWG 8.37 mm²
10 mm² 6 AWG 13.3 mm²
16 mm² 4 AWG 21.2 mm²
25 mm² 2 AWG 33.6 mm²
35 mm² 1 AWG 42.4 mm²
50 mm² 1/0 AWG 53.5 mm²
70 mm² 3/0 AWG 85.0 mm²
95 mm² 4/0 AWG 107 mm²

The row that catches people is 25 mm². It sounds like 4 AWG and it is not. 4 AWG is 21.2 mm², and the next size in this table with enough copper is 2 AWG.

These tables skip the odd gauges other than 1 AWG. They exist. This page sticks to the sizes the calculator works in.

Read the area, not the label

The gauge on the reel is a name. The area on the spec sheet is the copper. Three checks before you buy a reel.

B&S cable: use the listed area, not the gauge. B&S and AWG are the same series by name, but the number on a reel of battery cable tells you what it is called, not how much copper is in it. Put the mm² figure from the spec sheet into the calculator. If it comes in a little under the true AWG area, the calculator will tell you whether it still clears the run.

A cable sold by one millimetre figure, with no “squared”, is not telling you the copper. Treat that number as a diameter until the spec sheet says otherwise, and go looking for the conductor area in mm². If the listing does not give one, it is not telling you enough to size a run.

Copper clad aluminium. Wikipedia describes CCA as an aluminium core with a bonded copper coating, with higher resistance than solid copper of the same gauge. How much higher depends on whose aluminium figure you take. From the 20 °C resistivities in Wikipedia’s table it is somewhere around 55 to 65 percent more resistance for the same area, and the calculator uses the higher end of that. If the spec says CCA, size it as aluminium in the calculator, or buy copper.

If a reel has no conductor area anywhere on it or its spec sheet, leave it on the shelf.

Lugs are part of the cable

A crimp lug is made for one cable size, and that size is in one system or the other. Buy the lug for the cable in your hand, in the system it was sold in.

The gap is not small. A 25 mm² lug is made for about 18 percent more copper than a 4 AWG cable has. Go the other way and 25 mm² cable puts 18 percent more copper into a 4 AWG barrel than it was made for.

On every heavy lug:

  1. Strip to the depth of the barrel and no further.
  2. Crimp with the die marked for that cable size, not the nearest one.
  3. Pull hard on it before it goes anywhere near a battery. If it moves, cut it off and do it again.
  4. Adhesive-lined heat shrink over the barrel and onto the jacket.

Where this chart stops

It assumes copper, 12 volts and 68 °F (20 °C). It sizes the conductor for voltage drop and flags where the bundled heat rating overrules it. It does not size the fuse, choose the terminal or tell you the insulation rating your loom needs.

For anything off the grid, such as a different voltage, a hot space or aluminium, the DC wire size calculator does the same sum plus the heat check, and gives the AWG and metric answers side by side.

Sources

Where this guide states a fact rather than an opinion, it came from one of these. Product names are examples of a category, not endorsements, and nothing here is sponsored.

  1. American wire gauge - Wikipedia
  2. IEC 60228, conductors of insulated cables - Wikipedia
  3. Electrical resistivity and conductivity, table of materials - Wikipedia
  4. Voltage Drop in Conductor, Wire Sizing Chart - Blue Sea Systems
  5. AWG to mm² with bundled 12 V ampacity - VoltPlan
  6. Copper-clad aluminium wire - Wikipedia

Illustrations

The diagrams on this page are illustrations, drawn to explain a concept. They are not photographs of a real cabinet and they carry no measurements, because a diagram that looks precise and is not would be worse than no diagram at all. Anything on this site with numbers on it is generated from the underlying data.